Installing the SAN Switch 2/16
31
hp StorageWorks SAN Switch 2/16 Installation Guide
Attaching the Inner Slide Rails to the Switch
Use the following steps to secure each inner slide rail to the switch chassis.
Caution:
It is important to install the inner slide rails using the Phillips head,
8-32 x 3/16” screws supplied in the Rack Mount Kit. Installing screws longer
than 3/16” can damage the switch.
1. Position the inner slide rails with the flat side against the switch, oriented in
one of the following two ways:
Note:
HP recommends installing the SAN Switch 2/16 so that the port side of the
switch slides out the rear of the HP 9000 Series Rack (as described in step 1a below). In
this way, the switch faces the aisle where exhaust air is released. Air intake and exhaust
for all components in the rack should flow in the same direction.
a.
HP recommended method:
To allow the port side of the switch to slide out the rear of the rack:
Orient the inner slide rail with the end containing the lock release lever
towards the power supply end of the switch.
b.
To allow the power supply side of the switch to slide out the front of the
rack:
Orient the inner slide rail with the end containing the lock release lever
towards the port end of the switch.
2. Locate three Phillips head, 8-32 x 3/16” screws provided in the Rack Mount
Kit. Secure the inner slide rail to the switch, see
Figure 4
.
Summary of Contents for StorageWorks 2/16 - SAN Switch
Page 8: ...Contents 8 hp StorageWorks SAN Switch 2 16 Installation Guide ...
Page 60: ...Installing the SAN Switch 2 16 60 hp StorageWorks SAN Switch 2 16 Installation Guide ...
Page 74: ...Managing the SAN Switch 2 16 74 hp StorageWorks SAN Switch 2 16 Installation Guide ...
Page 86: ...Regulatory Compliance Notices 86 hp StorageWorks SAN Switch 2 16 Installation Guide ...
Page 94: ...Technical Specifications 94 hp StorageWorks SAN Switch 2 16 Installation Guide ...
Page 111: ......
Page 112: ......