Table 53 EVA 6x00 UPS loading
(continued)
% of UPS capacity
Watts
Enclosures
R12000
R5500
R3000
20.5
54.6
91.1
2460
6
17.3
46.2
77.2
2083
5
14.2
37.9
63.2
1707
4
11.1
29.5
49.3
1330
3
7.9
21.2
35.3
953
2
4.8
12.8
21.4
577
1
Table 54 EVA 4x00 UPS loading
% of UPS capacity
Watts
Enclosures
R3000
R1500
60.6
1637
4
46.6
94.0
1260
3
32.7
65.9
883
2
18.7
37.9
507
1
Environmental specifications
Table 55 Environmental specifications
50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft. altitude (1.8°
C/1,000 m)
Operating temperature
-40° to 150° F (-40° to 66° C)
Shipping temperature
10% to 90% non-condensing
Operating humidity
5% to 90% non-condensing
Shipping humidity
Up to 8,000 ft. (2,400 m)
Altitude
Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron or larger
Air quality
148
Non-standard rack specifications