Chapter 1
Choosing a Location 15
Cha
pter 1
Clearance
2/20, 4/40, and 6/60 series stand-alone configurations — located on or
below a table:
Back:
56 cm (22 in) for cooling and service.
Front:
86 cm (34 in) for operator access.
Sides:
56 cm (22 in) for removal of the external cover.
2/20, 4/40, and 6/60 series rackmounted configurations:
Back:
61 cm (24 in) minimum to allow adequate room for service
access.
Front:
86 cm (34 in) for operator access.
Sides:
56 cm (22 in) minimum
Height:
For ease of use and optimum safety, the top of the library
should be mounted approximately 120 cm (48 in) above the
floor.
8/80 and 10/100 series tape libraries
Back:
56 cm (22 in) minimum
Front:
191 cm (75 in) minimum
Sides:
5 cm (2 in) minimum
Floor rating
For 8/80 and 10/100 series tape libraries only.
A fully loaded library can weigh up to 325 kg (715 lbs). Each caster supports
up to 96 kg (213 lbs). To support the weight exerted on the floor by the casters,
the floor rating must meet or exceed 1,694 kg per square meter (347 lbs per
square foot).
Tip rating
For 8/80 and 10/100 series libraries only.
Do not tip the library more than 10°. Ensure that the location for the library has
a level surface.
Table 2
Location Criteria
Summary of Contents for Surestore E Tape Library Model 2/20
Page 1: ...hp surestore tape library 2 20 4 40 6 60 8 80 and 10 100 series user s guide ...
Page 2: ......
Page 6: ...4 Updates hp surestore tape library ...
Page 12: ...10 ...
Page 116: ...114 Retrieving Library Information Chapter 3 ...
Page 182: ...180 Upgrading Firmware Chapter 5 ...
Page 222: ...220 Library Error Codes Appendix ...
Page 236: ...234 ...
Page 237: ......