9
The following option cables are available. An updated product list is available on the World Wide Web at
http://www.hp.com/racksolutions/menu_products.html or in the HP Rack System Catalog.
P/N Volt/Current
Connector
Plug Type
Length
Jumper or Power cable
E7742A
250V / 10AMP
C13
C14
2.5m
Jumper
E7743A
125V / 10 AMP
C13
5-15P
90”
Jumper
E7798A
250V / 16AMP
C19
C20
2.5m
Power
E7802A
125V / 16AMP
C19
5-20P
4.5m
Power
E7803A
250V / 16AMP
C19
L6-20P
4.5m
Power
E7804A
250V / 16AMP
C19
C20
4.5m
Power
E7805A*
250V / 16AMP
C19
L6-30P
4.5m
Power
E7806A
240V / 16AMP
C19
none
4.5m
Power
E7807A
250V / 10AMP
C15
C14
.76m
Jumper
E7808A
240V / 16AMP
C19
IEC309
4.5m
Power
E7810A
250V / 16AMP
C19
GB16C
4.5m
Power
* For use with an Uninterruptable Power Supply (UPS) only.
Front Door
Standard is a right-opening, perforated front door with a lockable slam latch and sheet metal catch providing
ventilation and security. The rear door can be mounted to open from either the left or the right.
Support Rails
Some equipment is supported in the rack by support rails running from front to back. The rails are
screwed to the vertical columns
Only after securing a pair of rails with screws can equipment be installed.
The mounting slots in the columns are positioned to make support rail placement convenient in EIA units.
Rack Lifting Hooks
Four lifting hooks can be fitted to the top of the rack. Together, they can support the weight of a rack
loaded to maximum recommended gross weight. Each hook is capable of supporting 248.6 kg (547 lbs).
Maximum recommended gross weight is 995 kg (2188 lbs).
Side Panels
Sectioned side panels are injection molded PC-ABS plastic and come in two sizes: 9 EIA unit and 8 EIA
unit. All three racks use the 9 EIA unit panel at the bottom, and 8 EIA unit panels for the remainder. Pull
out-and-off side panels allow fast and easy access from either side for installation, servicing, and removal of
equipment.
Filler Panels
To ensure adequate cooling in racks using extractor fans, all unused front panel space must be covered
with blank filler panels and the rear door must be closed.
Filler panels are 1 U in height, and snap on and off without tools or mounting hardware.
Keyboard Tray
A pullout keyboard tray is available. The keyboard tray can be installed with either a sitting, or standing
operator in mind. The tray is mounted on rollers that allow it to be retracted or extended.
Chapter 2
Description