Specifications
HP Uninterruptible Power System T1000 XR and T1500 XR Models User Guide
C-5
HP CONFIDENTIAL
Codename: Sherman Part Number: 216164-002 Last Saved On: 8/19/02 4:21 PM
Battery Specifications
Table C-6: Battery Specifications—UPS T1000 XR Models
Feature Specification
Type
Sealed lead-acid; maintenance-free
Voltage
24 V Battery String
Charging
HP recommends 24 hours to allow full charge
Less than 3 hours to 90 percent capacity at default nominal utility voltage and no load
Table C-7: Battery Specifications—UPS T1500 XR Models
Feature Specification
Type
Sealed lead-acid; maintenance-free
Voltage
48 V Battery String
Charging
HP recommends 24 hours to allow full charge
Less than 3 hours to 90 percent capacity at default nominal utility voltage and no load
Environmental Specifications
Table C-8: Environmental Specifications—UPS T1000 XR and T1500 XR Models
Feature Specification
Operating temperature
10
o
C to 40
o
C (50
o
F to 104
o
F)
UL-tested at 25
o
C (77
o
F)
Non-operating temperature
-15
o
C to 55
o
C (5
o
F to 131
o
F)
Operating humidity
20% to 80% relative humidity (non-condensing)
Non-operating humidity
5% to 95% relative humidity (non-condensing);
38.7
o
C (101.7
o
F) maximum wet bulb temperature with no
cosmetic damage
Operating altitude
Up to 2,000 meters (6,562 feet) above sea level
Non-operating altitude
Up to 9,144 meters (30,000 feet) above sea level
Audible noise
Less than 46 dBA