Battery Maintenance
HP Uninterruptible Power System T2200 XR Models User Guide
4-5
4. Unfasten the plastic handle (1) and partially remove the battery pack (2).
5. Disconnect the battery cable by pressing the black tab on the connector (3) and pulling
apart (4).
2
1
3
4
Figure 4-4: Disconnecting the battery connector cable
6. Remove the battery pack. Set aside the used battery pack for proper disposal. Refer to
“Disposing of Used Batteries,” in this chapter.
WARNING: If the UPS is not powered down, immediately replace the battery pack. Do
not allow terminal connections to contact conductive materials. Do not touch or bring
tools in close proximity to terminals.
Installing a New Battery Pack
To install a new battery pack, reverse the steps in the section, “Removing the Battery Pack,”
in this chapter.
IMPORTANT:
Check clearance on battery terminal connections when reinserting the battery pack into
the battery compartment.