Figure 13: Installing an SFF drive
Figure 14: Installing an LFF drive
Verification
11.
Observe the newly installed drive and confirm that the fault LED is off and the status LED is solid
green.
The change in the LEDs may take several minutes as the drive is prepared for use by the system.
12.
Verify the state of the replacement drive.
From the SSMC interface, the drive ID that you just replaced will be removed from the list, and the
replacement drive will be assigned a new drive ID and be in a healthy state.
13.
From the SPOCC interface, verify that the
State
for the component and the storage system are
Normal
(green).
14.
After the component replacement, initiate
Check Health
on the storage system.
a.
From the SPOCC interface main menu, click
Support
in the left navigation pane.
b.
From the
Service Processor - Support
page, under
StoreServs
, click
Health Check
in the
Action
column.
15.
Install the bezel on the enclosure front.
a.
Insert the bezel into the enclosure right side.
b.
Press in the release tab.
20