Specifications

Environmental specifications

Table 1: Standard specifications

Specification

Value

Temperature range

1

Operating

0°C to 55°C (32°F to 131°F)

2

Nonoperating

-30°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating

8% to 90% at 28°C (82.4°F) maximum wet bulb temperature

Non-Operating

5% to 95% at 38.7°C (101.7°F) maximum wet bulb
temperature

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is
applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations.
Not rated for operation over 3,048 m (10,000 ft).

Fan failure might reduce performance.

Table 2: ASHRAE Class A4 specifications

Specification

Value

Temperature range

1

Operating

0°C to 45°C (32°F to 113°F)

10°C to 35°C (50°F to 95°F) when GPU is installed

2

Nonoperating

-10°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating

8% to 90% at 28°C (82.4°F) maximum wet bulb temperature

Non-Operating

5% to 95% at 38.7°C (101.7°F) maximum wet bulb
temperature

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 125 m (1.8°F per 410 ft) to 900 m (2,953 ft) is applicable.
No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations except for
rotating hard drives. PCI cards must be rated for continuous operation with 60°C cooling air. Not rated for operation over 3,048 m (10,000
ft).

Fan failure might reduce performance.

44  Specifications

Summary of Contents for Edgeline EL8000

Page 1: ...October 2019 Edition 1 Abstract This document is for the person who installs administers and troubleshoots servers and storage systems Hewlett Packard Enterprise assumes you are qualified in the serv...

Page 2: ...m Hewlett Packard Enterprise required for possession use or copying Consistent with FAR 12 211 and 12 212 Commercial Computer Software Computer Software Documentation and Technical Data for Commercial...

Page 3: ...t 14 Installing the four post rack mount kit 17 Associated hardware procedures 21 Powering down the system 21 Powering up the system 21 Removing the blade from the chassis 21 Installing the server bla...

Page 4: ...bleshooting 35 Important safety information 35 Symbols on equipment 35 Warnings and cautions 36 Electrostatic discharge 37 Collecting symptom information 38 Preparing the EL8000 system for diagnosis 3...

Page 5: ...port and other resources 49 Accessing Hewlett Packard Enterprise Support 49 Accessing updates 49 Customer self repair 50 Remote support 50 Warranty information 50 Regulatory information 50 Documentati...

Page 6: ...rovisioning and remote system management The HPE EL8000 Chassis Manager is a remote management tool embedded in certain HPE Edgeline systems The software allows system administrators to remotely confi...

Page 7: ...to configure the system a Verify network connectivity b Plan for network address 6 Connect to the Edgeline EL8000 Chassis Manager and configure the system using one of the available methods Connect to...

Page 8: ...ly with local and regional electrical regulations governing the installation of information technology equipment by licensed electricians This equipment is designed to operate in installations covered...

Page 9: ...lane assembly 3 HPE Edgeline EL8000 Converged Edge chassis 4 HPE ProLiant e910 1U server blade 5 HPE ProLiant e910 2U server blade 6 Chassis Manager 7 Power supplies HPE Edgeline EL8000 Converged Edge...

Page 10: ...talled The EL8000 chassis can accommodate up to two 2U HPE ProLiant e910 server blades EL8000 Chassis with both 1U and 2U server blades installed The EL8000 chassis with one 2U and two 1U server blade...

Page 11: ...wer supply off Solid Amber Power supply failed overvoltage undervoltage overtemperature overcurrent short circuit fan failed or input overvoltage protection Flashing Amber Power supply error Off No po...

Page 12: ...ber Power supply failed overvoltage undervoltage overtemperature overcurrent short circuit fan failed or input overvoltage protection Flashing Amber Power supply error Off No power present or standby...

Page 13: ...tem Description 1 Management Network port 2 Blade maintenance network port 3 Antenna 1 4 Chassis manager USB ports 5 Antenna 2 6 Chassis UID Button LED 7 Chassis Health LED Component identification 13...

Page 14: ...19 in and 23 in depth Prerequisites Before you perform this procedure make sure that you have the following items available T 10 Torx screwdriver T 25 Torx screwdriver Procedure 1 Install the brackets...

Page 15: ...3 Install the rack tray into the brackets a Install the tray into the brackets b Install two screws in the front and rear brackets each and then tighten them Rack mount option 15...

Page 16: ...Tighten the eight screws that were loosened in step 2 4 Install the chassis on the rack tray a Place the chassis on the rack tray b Secure the chassis with two screws on the front 16 Rack mount optio...

Page 17: ...ition is preferred when the cables connected to the chassis are at the rear of the rack Rear chassis rack mount This mounting position is preferred when the cables connected to the chassis are at the...

Page 18: ...orx screwdriver Procedure 1 Identify the mounting location install the tray bracket and stop the screw in correct location Forward chassis rack mount Rear chassis rack mount 2 Install the rails into t...

Page 19: ...3 Install the rack tray on the rails and then secure it Make sure that the tray slides under the bracket 4 Place the chassis on the tray and then secure it Rack mount option 19...

Page 20: ...20 Rack mount option...

Page 21: ...d on the blade Enter the set power off b slot at the chassis manager CLI See the HPE Edgeline EL8000 Converged Edge System Chassis Manager CLI User Guide on the HPE website for details on CLI commands...

Page 22: ...e server blade Installing the server blade into the chassis The HPE Edgeline EL8000 Converged Edge chassis supports HPE ProLiant e910 Server Blade Permissible server blades configurations Up to four 1...

Page 23: ...performing this procedure make sure that you have the T 15 Torx key available Procedure 1 Align the blade and install it in the chassis a Insert the blade in the chassis b Close the latch on the serve...

Page 24: ...gned IP address or hostname Note that since there is no serial port available on the Edgeline EL8000 Chassis Manager you may need to also use a USB to RS232 adapter Connecting to the web interface usi...

Page 25: ...sion on the system you are using to configure Use the following settings Specification Value Serial Line Appropriate for the system you are using to connect Baud rate 115200 Data bits 8 Parity None St...

Page 26: ...elect Tools Internet options 3 Click Security 4 Click Custom level 5 In the Scripting section set Active scripting to Enable 6 Click OK 7 Refresh your browser window Logging in to the web interface Pr...

Page 27: ...erface require you to scroll down to see all the options available or to reach an Apply button Confirmation status and error messages display at the top of the page so remember to scroll back up to th...

Page 28: ...m IPv6 Default Gateway When IPv6 is enabled the gateway is the default IP address Edgeline EL8000 Chassis Manager uses to access the network When not enabled this entry is blank Speed Mbps The speed o...

Page 29: ...e IP address 3 Enter the Domain Name if DHCP is not configured 4 Click Apply Host name and domain name limitations The Subsystem Name Host name is initially set at the factory and is listed on the cha...

Page 30: ...on and DNS Configuration section are automatically assigned When the system is rebooted these automatic assignments might change Static IPv4 Address Configuration settings IPv4 Address The Edgeline EL...

Page 31: ...hen accessing a client application It is useful when both IPv4 and IPv6 service addresses are configured for Edgeline EL8000 Chassis Manager client applications This setting also applies to lists of a...

Page 32: ...llowing information for each listed firmware type Firmware name The category name of the firmware Firmware version The currently installed version number of the firmware Updating firmware While firmwa...

Page 33: ...l force all open sessions to the Edgeline EL8000 Chassis Manager to log out If this happens log in again and delete stored files until the repository storage is below the maximum capacity Installing a...

Page 34: ...ge System Chassis Manager User Guide at http www hpe com support EL8000 CM UserGuide en Access Edgeline EL8000 Chassis Manager from practically anywhere or use a link on the Blades page to access the...

Page 35: ...ety information in the following sections before troubleshooting the system Important safety information Before servicing this product read Safety and Compliance Information for Server Storage Power N...

Page 36: ...bassembly module level repair Because of the complexity of the individual boards and subassemblies no one should attempt to make repairs at the component level or to make modifications to any printed...

Page 37: ...e system you must provide at least 7 6 cm 3 0 in of clearance at the front and back of the server CAUTION The server is designed to be electrically grounded earthed To ensure proper operation plug the...

Page 38: ...support ahsv docs Preparing the EL8000 system for diagnosis Procedure 1 Verify that the system is in the proper operating environment with adequate power air conditioning and humidity control 2 Record...

Page 39: ...Symptom The HPE Moonshot 1500 CM module powers on without being fully inserted to the chassis If the CM is not fully inserted it may cause the fan to make load noise and the CM fails to communicate w...

Page 40: ...Packard Enterprise is committed to providing our customers with information about the chemical substances in our products as needed to comply with legal requirements such as REACH Regulation EC No 190...

Page 41: ...e harmful interference This device must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to comply with the limits fo...

Page 42: ...terference to cochannel mobile satellite systems Radio Frequency RF Exposure Information This equipment complies with radio frequency RF exposure limits adopted by the Federal Communications Commissio...

Page 43: ...de distance entre la source de rayonnement et votre corps Cet metteur radio IC 24448 EL8000530S a t approuv par Industrie Canada pour fonctionner avec les types d antennes num r s ci dessous avec le g...

Page 44: ...Fan failure might reduce performance Table 2 ASHRAE Class A4 specifications Specification Value Temperature range1 Operating 0 C to 45 C 32 F to 113 F 10 C to 35 C 50 F to 95 F when GPU is installed2...

Page 45: ...PCI cards must be rated for continuous operation with 60 C cooling air Solid state drives must be rated for continuous operation with 65 C cooling air Not rated for operation over 3 030 m 10 000 ft Me...

Page 46: ...582 at 264 VAC Power supply output Rated steady state power 1500 W at 200 VAC to 240 VAC 1400 W at 110 VAC to 120 VAC 1260 W for 100 VAC Maximum peak power 1500 W at 200 VAC to 240 VAC 1400 W at 110 V...

Page 47: ...circuit to the earthing conductor at the equipment If this connection is made all of the following must be met This equipment must be connected directly to the DC supply system earthing electrode cond...

Page 48: ...info EIL Hewlett Packard Enterprise Edgeline Documentation www hpe com info edgeline docs Hewlett Packard Enterprise Edgeline Information www hpe com info edgeline Hewlett Packard Enterprise OT Link a...

Page 49: ...tes through the product interface Review your product documentation to identify the recommended software update method To download product updates Hewlett Packard Enterprise Support Center www hpe com...

Page 50: ...Proactive Care information HPE Get Connected www hpe com services getconnected HPE Proactive Care services www hpe com services proactivecare HPE Proactive Care service Supported products list www hpe...

Page 51: ...m info ecodata For Hewlett Packard Enterprise environmental information including company programs product recycling and energy efficiency see www hpe com info environment Documentation feedback Hewle...

Page 52: ...line interface CPLD complex programmable logic device DDNS dynamic DNS DHCP dynamic host configuration protocol DNS domain name system iLO integrated Lights Out SSD solid state device UID unit identi...

Reviews: