4. Operation
4.1 Start-up and normal operation
To start the UPS:
1.
Verify that the UPS power cord is plugged in.
The UPS front panel illuminates and shows the HPE logo.
2.
Verify that the UPS status screen shows .
3.
Press
the button on the UPS front panel for at least 2 seconds.
The UPS front panel changes status to "UPS starting...".
4.
Check the UPS front panel for active alarms or notices. Resolve any active alarms before
continuing. See "5.1 Troubleshooting".
If the indicator is on, do not proceed until all alarms are clear. Check the UPS status from the front
panel to view the active alarms. Correct the alarms and restart if necessary.
5.
Verify that the indicator illuminates solid, indicating that the UPS is operating normally and any loads
are powered and protected.
The UPS should be in Normal mode.
4.2 Starting the UPS on battery
Before using this feature, the UPS must have been powered by utility power with output enabled
at least once.
NOTE:
Battery start can be disabled. See the "Cold start" setting in "ON/OFF settings".
To start the UPS on battery:
1.
Press the button on the UPS front panel until the UPS front panel illuminates and shows
a status of "UPS starting...".
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid.
The UPS supplies power to your equipment.
2.
Check the UPS front panel for active alarms or notices other than the "Battery mode" notice
and notices that indicate missing utility power. Resolve any active alarms before continuing.
For more information, see "5.1 Troubleshooting".
4.3 UPS shutdown
To shut down the UPS:
Press
the button on the front panel for three seconds.
The UPS starts to beep and shows a status of "UPS shutting OFF...". The UPS then transfers to Standby
mode, and the indicator turns off.
4.4 Operation on battery power
Transfer to battery power
•
The connected devices continue to be supplied by the UPS when AC input power is no longer available.
The necessary energy is provided by the battery.
•
The and
indicators illuminate solid.
•
The audio alarm beeps every ten seconds.