HRW HPE8884BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice
Page 10 of 23
Display Navigation
Function
Enter
Result
Options /
Comments
Display Control
Commands
M
Display
I/O
summary screen
M
P
Display
Point
status list
Enter P or P1 to display the first 21 Objects. Enter
Pxx (where ‘xx’ is a point #) to display any other
point and the following 20 points
S
Return to User
Summary
display
S
SS
Screen
Static
Disable 10 sec live update
SL
Screen
Live
Enable 10 sec live update
SLLD
Screen Line Logic
Display
Enable/Disable display of object numbers and
screen line numbers in the summary display
Summary Screen Setting
Function
Line
Method
Result
Options /
Comments
Summary Display
Lines & dynamic point
setting
SL1…32
SL(x)x=abc…
Assign
Screen Line
text as information or in
relation to SP1…32
Alpha/numeric, 40
characters max.
SP1…32
SP(x)x=nnn
Assign
Screen Point
dynamic point value
Object #
SLL1…32
SLL(x)x=nnn
Assign
Screen Line Logic
point who’s value
>0 will cause the related screen line to appear
at the top of the display (alarm state for
instance)
Object #
Manual Override / Release
Values that have been manually set will be indicted in HyperTerminal by an
M
tag next to the displayed
value. The BACnet priority level = 9
Manualled physical inputs (points 1…8 & 17…24) will revert to ‘Auto’ after being Released or after a
power reset. Physical outputs will retain the Manual setting after a power reset if the Manual state is
Written (
W
) before being released, thereby making the Manual state the power-up default state.
Function
Enter
Result
Options /
Comments
Manual a
Digital
Object #=1, 0
Digital on or off
1=On
0=Off
Example: 37=1
Manual an
Analogue
Object #=0…
n
0…100% block output
Block range 0….max
Example: 25=50 (AO1 50% output
/ 5Vdc output)
Release
Manual
overrides back
to ‘Auto’
*
R
R=1…112
Inputs will return to auto state/value.
Other points will remain at manualled
state/value until power reset or
commanded
Example 1: R
All overrides are cleared
Example 2: R=9
DO1 (point 9) only return to Auto
Reset pulse
accumulator
100…800=6
1700…2400=6
DI or UI with pulse accumulator
config. (UI or DI setting 6) is reset to
zero
Example: 800=6