HRW HPE8884BN V402 Manual 150622.docx E. & O. E. / Subject to change without notice
Page 20 of 23
Dimensions
If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of
the device is 45.5mm
Technical Data
Inputs/Outputs
8 DI
8 DO
8 UI
4 AO
Sensor/Transmitter Wiring
Network Wiring
Comms Speed
RS485 Driver
Power Supply
Conformity & Approvals
Operating Temperature Range
Storage Temperature Range
Humidity Range
Dimensions
- Voltage-free contact closure, 1mA
- Binary DI or pulse counting up to 10Hz (pulse value saved hourly)
- 24Vac, 3A in-rush, 300mA holding max., minimum load 10mA
- DI with pulse counting up to 10 Hz (pulse value saved hourly)
- NTC/PTC (min. 1kΩ)
- 0-5Vdc, 0-10Vdc, 0-20Vdc, 0.01 Volt resolution
- 0…20Ma, 4…20mA, 0.016mA resolution (requires external
18…28Vdc loop power supply)
- 0-10Vdc, 0.04 Volt resolution, 1.5mA (min 6.6kΩ impedance)
Shielded twisted pair (shield grounded)
Belden 9841 low capacitance twisted pair for RS485 networks
(b foil shield, shield continuous throughout the network and
grounded at network origin)
RS485 - 2400, 4800, 9600, 19200, 38400, 57600, 76800 baud
Isolated 1/8
th
load, 256 nodes over max. 1.2km without repeater
24Vac, 50/60 Hz, max. 5VA without DO load
60VA MAX. when DO’s supplied via the device’s 24Vac terminals and
fully loaded @ max. 300mA / DO
BTL Listing 23710
UL 916
CAN/CSA C22.2 #205-M1983
FCC Part 15 Subpart B Class B
EN 55022, EN 55024, EN 61000-3-2, EN 61000-3-3
0…50ºC (32…122ºF)
-5…75ºC (-40…167ºF)
10…95%rH (non-condensing)
115mm H x 226.5mm L x 34.5mm D