HRW HPD0440BNMR V401 Manual 111116.doc E. & O. E. / Subject to change without notice Page 17 of 43
Administration Commands
BACnet & General
Function
Enter
Result
Options /
Comments
Start
communicati
on
TTTTT(TTT…)
Display of configuration
and I/O status
With the Caps Lock on, hold the T key down
until the screen updates with HPE data. It is
not necessary to press the enter key to start
communication.
Download
textfile
DE
Make ready for file path
Menu: Transfer > Send textfile >
file
Reset to
Factory
Default
FD=1
Reset to ex-factory settings
FD will be displayed in the top line of the I/O
summary screen after reset
Set node
address
(MAC)
98=1…255
Network node number is
assigned
Example: 98=25
1…127 the device will be a ‘token passing
master’
128… 255 the device will become a network
slave after power reset
Set system
Device
Instance
DI=0…4194303
Unique Device Instance is
assigned
Example: DI=401025 (building 4, network 1,
node 25)
Set baud rate
99=…
Network comms speed is
set
2400, 4800,
9600
, 19200, 38400, 57600,
76800
Example: 99=9600
After changing comm. speed it will be
necessary to reconnect with HyperTerminal
at the new comm. speed to save (write) the
change!
Set
Maximum
Master
address
MM=1…127
Highest Master device
address on the network is
registered
Next address searching limited to MM
address
Set Sys.
Vendor ID
(
S
ys
V
id)
SV=0…255
System vendor specific
features may be available
SV=0 applies generic BACnet operation. If
an entered ID is not implemented then the
generic operation will be applied
Zero the
Reset
counters
95=0, 96=0, 97=0
Each Reset counter is
zeroed
Factory diagnostics
Resets = <95> <96> <97>
Rx timeout, Tx timeout, Hardware reset
Write values
as default
W
Changes written.
Always do this after making changes that
you wish to be permanent
Exit
communicati
on
X
Communication with
HyperTerminal no longer
active
Auto X after 240sec without key entry.
After
eXit unplug the HPECOM cable to allow
network communication to take place