background image

 
 
 
 
 

HRW HPE-BNP1BUS V401 Manual 120201.doc            E. & O. E. / Subject to change without notice  Page 18 of 18 

Notes: 

Summary of Contents for HPE-BNP1BUS

Page 1: ...ed to the gateway for read write access of up to 250 data points Typical Applications BACnet MS TP network integration of P1 devices System 600 APOGEE Insight TEC ATEC SCU DPU DLM MEC Point Expansion units HRW HP P1 devices Feature Summary FIND function for initial network device application identification Diagnostic function for comms verification and trouble shooting Continuous poll for point st...

Page 2: ...IN TO TERMINAL MODE 5 BACNET CONFIGRATION COMMANDS 6 P1 CONFIGURATION COMMANDS 7 P1 INTEGRATION 8 FIND 8 SENSOR TYPE SCALING TABLE 9 Standard Sensor Types 10 POINT TYPE 10 DATA POINT CONFIGURATION 10 DATA BASE MAPPING TOOL 12 POINT CONFIGURATION 12 SCALING TABLE CONFIGURATION 13 DOWNLOAD TEXT FILE 14 SCAN P1 FLN NETWORK 14 DIAGNOSTIC DISPLAY 14 INSTALLATION COMMISSIONING 15 CONNECTIONS 16 DIMENSIO...

Page 3: ...It is important to have the P1 device manufacturer s manual available to assist with P1 point address and type scaling Each point of the gateway data base consists of 1 Device addresses 2 Point numbers within the device addresses 3 Sensor type relating to each point as defined in the scaling table 4 A point type LDI LDO LAI LAO represented as a number 1 4 respectively BACnet Priority Array The BAC...

Page 4: ...ue are recommended A USB port Serial comm port DB9 converter may be required for HPECOM if the PC being used does not include a Com 1 serial port The following settings reflect HyperTerminal Please contact us if you require assistance setting up Indigo HyperTerminal Settings For successful communication between HyperTerminal and the device initial Properties setup of HyperTerminal should be as per...

Page 5: ...rk operation Saving HyperTerminal Settings For ease of connection it is recommended to save the HyperTerminal setup for each baud rate you may wish to use with an easily recognised configuration name For example HPECOM 24 2400 HPECOM 48 4800 HPECOM 96 9600 HPECOM 19 2 19200 HPECOM 38 4 38400 HPECOM 57 6 57600 Break in to Terminal Mode When HyperTerminal is running and the HPECOM cable is connected...

Page 6: ... it will be necessary to reconnect with HyperTerminal at the new comm speed to save write the change Set Maximum Master address MM 1 127 Highest Master device address on the network is registered Next address searching limited to MM address Set Sys Vendor ID SysVid SV 0 255 System vendor specific features may be available SV 0 applies generic BACnet operation If an entered ID is not implemented th...

Page 7: ...int to NULL R 4 253 Specified point is Released to NULL priority 17 will be displayed at the extreme right of the target data point configuration line to signify NULL priority Enable P1 subnet communication E Toggles Enabled Disabled of M Bus Subnet communication Default Disabled to allow easy configuration when no M Bus devices are connected Always Enable when M Bus devices are connected and poin...

Page 8: ... to decide which points are available in each P1 device simplifying the creation of the point database of the gateway Enter F to start the Find function The Find function will automatically poll each possible P1 address to find how many devices are on an existing network Each address is polled twice in the event a device does not respond on it s first polling Once devices are identified they will ...

Page 9: ...able is revealed Customisation can be made directly over HyperTerminal or by download of a configuration file taken from the address calculator tool While displaying the table using a row column address matrix each value in the table may be customized For instance to change Type 1 row 1 so that it is applicable for F instead of C then 1 Slope of 0 25 a Units multiplier 25 therefore enter 13 25 row...

Page 10: ...HRW 14 Digital Normally Closed 1 0 Type 15 HRW 15 Digital Toggle 1 0 Point Type Point Type programming value defines the P1 point in the gateway so that the gateway knows what BACnet object type should be used when making the point data available on the BACnet MSTP network P1 Point Type Description Gateway Point Type Gateway Tag BACnet Object Type LDI Digital Input 1 DI BV LDO Digital Output 2 DO ...

Page 11: ... by default indicted by value 17 on the right side of the display To command from the BACnet BMS then commands must be sent with a priority of 16 or higher After downloading your point database and connecting the network always remember to Enable the P1 network comms and Write the Enabled state so that comms is automatically reinstated after a power failure Normally the gateway will poll the netwo...

Page 12: ...ich can be downloaded to the gateway as a text file txt Point Configuration In the example below two P1 devices are configured each with three input points to be read Once the information is properly entered in the tool the resultant point configuration data in the Download column may be copied to Notepad for saving as a text file and download to the gateway The last row of the download data 10000...

Page 13: ...he Download column This download data is then copied to a text file for download over HyperTerminal using the same process as used for the point database download The reference Slope and Intercept values are taken from the P1 device documentation Entering these two values automatically calculates the Base value required by the HPE BNP1BUS The 10 s Multiplier and 1 s Multiplier values must be manua...

Page 14: ...rminal mode any scanning of the P1 network will only occur after pressing Enter as a separate action to any other settings After exit from terminal mode the scanning will occur automatically After pressing Enter wait for the display to refresh with read values this may take some time if the network contains many devices and data points Diagnostic Display For trouble shooting the Diagnostic functio...

Page 15: ...en at each device should be continuously connected via the S terminal of the device note that the device s S terminal has no electrical connection to the device it merely acts as a junction terminal for the purpose of screen continuity The RS485 cable should avoid cable routes that run with power cables Where the RS485 cable must cross power cables then they should cross at 90 avoiding parallel ru...

Page 16: ...c E O E Subject to change without notice Page 16 of 18 Connections Dimensions If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45 5mm P1 Network BACnet RS485 HPE BNP1BUS ...

Page 17: ...int gateway BACnet MS TP integration of P1 FLN devices for control panel mounting Standard package 40 units per carton Accessories HDA0002 DIN rail adapter brackets factory fitted HPECOM Configuration cable DB9 RJ11 HPECOMU Configuration cable USB RJ11 U232 P9 RS232 DB9 USB adapter cable Other HP_BN Series Devices HPC0662BN Universal Controller 12 Point BACnet MS TP 24Vac HPC8884BN Universal Contr...

Page 18: ...HRW HPE BNP1BUS V401 Manual 120201 doc E O E Subject to change without notice Page 18 of 18 Notes ...

Reviews: