MANUAL
HK2 – HK4 25-08-2014
Page
32
3.13.2
Installation diagram – simple system
1 : HK2/HK3
2 : Return temperature unit
3 : Storage tank O 1500 L/2500L
4 : System pump
5 : DHW tank
6 : Themostatic valve
7 : Thermostat
8 : Expansion vessel 150 L/200L
9 : Safety group
10: Automatic vent
11: 1” ON/OFF valve
12: ¾” ON/OFF valve
13 : 3-way valve – spring return
The purpose of the 3-way valve is to minimize the system volume as the heating system is requiring high energy input.
As the storage tank sensor measures a temperature below 40 °C the valve shifts to the top of the tank.
as the temperature in this position comes above 45 °C the valve shift to the bottom of the tank.
Both the shift up temperature (deafult 40 °C (n7)) and the hysteresis (default 5 °C (n8)) can be adjusted.