background image

HLogic Security Technology Co., Ltd

www. hstfire .com

Document Ref: M7285-01

Issue:1.0

07/2016

Connection of mode 1 of sounder strobe

Note:

The mode 1 is used in low currents in 2-wires loop without external power supply, recommended to

connect the number of sounder strobe not more than 15 pcs per loop. The mode1 has sounder

function only without strobe function.

All wiring must conform to applicable local codes, ordinances, and regulations. Written the address

of sounder strobe before mounting and wiring by programmer.

1. Select

Mode 1

(set the pin1 and pin2 of the

Mode Selection

to connected on the sounder

strobe) as figure 4.

2. Connect the loop (+) and loop (–) wires of addressable panel to the Terminal L+ and

Terminal L-.

3. Connect the Earth wire of panel to Terminal E.

4. Program the address on the sounder strobe per job drawings.

5. Install the sounder strobe in the desired mounting location.

Connection of mode 2 of sounder strobe

Note:

The mode 2 is used in normal with sounder and strobe function for 4-wires addressable system.

All wiring must conform to applicable local codes, ordinances, and regulations. Written the address

of sounder strobe before mounting and wiring by programmer.

1. Select

Mode 2

(set the pin2 and pin3 of the

Mode Selection

to connected) on the sounder

strobe as figure 5.

2. Connect the loop (+) and loop (–) wires of addressable panel to the Terminal L+ and Terminal L-.

3. Connect the Earth wire of panel to Terminal E.

4. Connect the V+and V– wires of external supply to the Terminal V+ and Terminal V-.

5. Program the address on the sounder strobe per job drawings.

6. Install the sounder strobe in the desired mounting location.

Figure5

Connection of mode 2

Maintenance

Apart from regular testing of the sounder strobe, as part of the scheduled maintenance of the fire
alarm system, no additional maintenance is required.

Figure4

Connection of mode 1

Sounder Strobe

Fir

e

ala

rm

co

ntr

ol

pa

ne

l

Loop

Out+

Out-

Earth

In+

In-

Earth

Next devices

Sounder Strobe

Fir

e

ala

rm

co

ntr

ol

pa

ne

l

Loop

Out+

Out-

Earth

In+

In-

Earth

Next devices

V+
V-

External power supply

24-32VDC Output

HST

17

A-201 CPR 2017

17