lp-548 Rev. 000 Rel. 004 Date 1.11.19
8
MODBUS
Heating Appliance
Water Heater
BACNET
Address
Description
Description
Object Type Object Instance
Unit
Resolution
Input Registers
Input Registers
30056
Vortex 2 flow
N/A
AI
55
LPM
0.1
30057
Vortex 2 temp
N/A
AI
56
Deg F
0.1
30091
Total Faults
N/A
AI
90
1
30092
Total Last Faults
N/A
AI
91
1
30093
Run Hours CH
AI
92
x5
30094
Run Hours DHW
AI
93
x5
30095
Run Hours Cas CH
N/A
AI
94
x5
30096
Run Hours Cas DHW
N/A
AI
95
x5
30097
Power Hours
AI
96
x5
30099
Start Counter
AI
98
1
30100
Start Counter
AI
99
1
Holding Registers
40001
Configuration
Configuration
AV
0
See
Configuration
Bits Section
1
40002
Coils
Coils
AV
1
1
40003
0-10 volt / rate / setp
0-10 volt / rate / set
AV
2
V
0.1
40004
DHW setpoint
DHW set
AV
3
Deg F
0.1
40005
DHW temperatur
DHW temp
AV
4
Deg F
0.1
40006
Outdoor temp.
Outdoor Sensor
AV
5
Deg F
0.1
40007
Sys supply temp.
N/A
AV
6
Deg F
0.1
40008
Sys rtn temp.
N/A
AV
7
Deg F
0.1
40009
I4 for direct
N/A
AV
8
Deg F
0.1
40010
CH post purge
N/A
AV
9
Seconds
1
40011
DHW post purge
N/A
AV
10
Seconds
1
40012
Pump 4 Speed
N/A
AV
11
%
0.1
40014
Extra out ECS
N/A
AV
13
%
0.1
Table 8 - MODBUS and BACnet Memory Map - *Only Valid Valves During Heating Cycle
Address 40001/AV0 contains configuration bits sent from the BMS to the appliance. These bits tell the appliance to use its own internal inputs,
or inputs from the BMS. When a bit is set to 1, the appliance will ignore the corresponding value contained internally and expect the BMS to
write that value into the holding registers. The configuration bits are as follows:
C. Configuration Bits
Holding Register 40001 / AV0
Decimal Value
HEX Value
Selected Signal (Register) to Write to
0 = Taken from Control
1 = Taken from MODBUS
B0 (LSB)
1
01
Boiler enable (40002 / AV1)
0/1
B1
2
02
Tank enable (40002 / AV1)
0/1
B2
4
04
Rate command / 0-10V input / setpoint command
(40003 / AV2)
0/1
B3
8
08
DHW setpoint (40004 / AV3)*
0/1
Holding Register 40001 / AV0
Decimal Value
HEX Value
Selected Signal (Register) to Write to
0 = Taken from Control
1 = Taken from MODBUS
B4
16
10
DHW temperature (40005 / AV4)
0/1
B5
32
20
Outdoor temperature (40006 / AV5)
0/1
B6
64
40
System supply temperature (40007 / AV6)
0/1
B7
128
80
System return temperature (40008 / AV7)
0/1
B8
256
100
I4 offset (40009 / AV8)
0/1
B9
512
200
CH post purge (40010 / AV9)
0/1
B10
1024
400
DHW post purge (40011 / AV10)
0/1
B11
2048
800
Pump 4 speed (40012 / AV11)
0/1
B12
4096
1000
Pump 5 speed (40013 / AV12)
0/1
B13 (MSB)
8192
2000
Extra 0-10V output (40014 / AV13)
0/1