51
LP-387 REV. 12.15.14
4. It is important to support gas piping as the boiler is not designed to structurally support a large amount of weight.
5. Purge all gas lines thoroughly to avoid start up issues with air in the lines.
6. Sealing compound (pipe dope) must be used and approved for gas connections. Apply sparingly, and only to the male threads. Care
must be taken when applying compound to prevent blockage or obstruction of gas flow which may affect the operation of the boiler.
Failure to apply pipe sealing compound as detailed above could result in substantial property damage, severe personal injury, or death.
CSA / UL listed flexible gas connections can be used when installing the boiler. Flexible gas connections have different capacities and
must be sized correctly for the connected boiler firing rates. Consult with the flex line supplier to assure the line size is adequate for the
job. Follow local codes for proper installation and service requirements.
Never use an open flame (match or lighter) to check for gas leaks. Use a soapy solution to test connection. Failure to use a soapy
solution test or check gas connection for leaks could result in substantial property damage, severe personal injury, or death.
Use a two-wrench method when tightening gas piping near the boiler and its piping connection: One wrench to prevent the boiler gas
line connection from turning; the second to tighten the adjacent piping. Failure to support the boiler gas piping connection could
damage the boiler beyond repair. Such damage IS NOT covered by warranty.
C. CHECK INLET GAS PRESSURE
The gas valve is equipped with an inlet gas pressure tap that can be used to
measure the gas pressure to the boiler. To check gas pressure, perform the
steps listed below:
1.
IMPORTANT!
Before you connect to the inlet pressure, shut off the gas and
electrical power to boiler.
2. Loosen the pressure tap with a small screwdriver. Refer to Figure 27 for
location.
3. Each boiler is equipped with a needle valve that will accept a 5/16 ID hose to
connect to a digital manometer or liquid gauge designed to measure incoming
pressure from 0-
35” w.c. See 7.
4. Turn on the gas and power up the boiler.
5. Put the boiler into manual test mode (details on test mode are in Part 11
Section D). In service mode, monitor pressure to assure it does not drop below
1 inch from its idle reading. If gas pressure is out of range or pressure drop is
excessive, contact the gas utility, gas supplier, qualified installer, or service
agency to determine correct action that is needed to provide proper gas pressure to the boiler. If Gas Pressure is within normal range
proceed to Step 6.
6. Exit test mode, then turn power off and shut off gas supply at the manual gas valve before disconnecting the hose from the gas
monitoring device. Tighten screw on the pressure tap and turn gas on. Check for leaks with soapy solution. Bubbles will appear on the
pipe to indicate a leak is present.
Ensure the pressure tap screw is properly tightened to prevent gas leaks. Failure to do so could cause substantial property damage,
severe personal injury, or death.
The gas piping must be sized for the proper flow and length of pipe to avoid pressure drop. The gas meter and regulator must be
properly sized for the total gas load. If you experience a pressure drop greater than 1" w.c. (.87 kPa), the meter, regulator or gas line
Summary of Contents for EFT-110
Page 14: ...14 LP 387 REV 12 15 14 SPECIFICATIONS AND DIMENSIONS Figure 2 LP 387 K ...
Page 24: ...24 LP 387 REV 12 15 14 Figure 8 Piping Symbol Legend ...
Page 58: ...58 LP 387 REV 12 15 14 Figure 32 Cascade Master and Follower Wiring ...
Page 59: ...59 LP 387 REV 12 15 14 Figure 33 Internal Connection Diagram LP 293 J ...
Page 82: ...82 LP 387 REV 12 15 14 EFT 55 80 110 PARTS BREAKDOWN Figure 36 Replacement Parts LP 387 J ...
Page 88: ...88 LP 387 REV 12 15 14 ...
Page 89: ...89 LP 387 REV 12 15 14 ...