35
C. REQUIREMENTS FOR INSTALLATION IN CANADA
1. Installations must be made with a vent pipe system certified to ULC-S636. IPEX is an approved vent
manufacturer in Canada supplying vent material listed to ULC-S636. Additionally you may use AL29-4C stainless
steel venting to comply with Canadian requirements.
2. The first three (3) feet of vent pipe from the appliance flue outlet must be readily accessible for visual
inspection.
3. The components of the certified vent system must not be interchanged with other vent systems or unlisted pipe
/ fittings.
Cellular foam core piping may be used on air inlet piping
only
.
NOTE:
The use of double-wall vent or insulated material for the air inlet is recommended in cold climates to
prevent the condensation of airborne moisture in the incoming combustion air.
You must not use “B” vent in an exhaust application. “B” vent is for intake applications
ONLY
. Using “B” vent in an
exhaust application will result in serious injury or death.
Figure 11 - NOTE: Drawing is meant to demonstrate system venting ONLY.