83
Fault Code F13
FAN SPEED ERROR
F13
PUMP ON
The fan is not running at the speed that the control
has commanded it to run at. The fan speed had
been more than 30% faster or slower than the
commanded speed for more than 10 seconds. The
red light will display and the word LOCKOUT will
flash. This code indicates a serious safety issue and
the boiler will not restart until the cause is
determined by a technician and he pushes the
RESET button on the display. During this lockout
fault, the pump will be on as indicated on the second
line.
1. Check the combustion air fan wiring.
2. Measure the DC voltage from the red fan wire to
ground while it is connected to the fan. It should be
between 24 to 40 volts. If it is lower than 24 volts,
check for excessive external loads connected to the
boiler sensor terminals. Disconnect the 5 pin plug
from the fan and check the voltage on the red wire
again. If it is now between 24-40 volts, replace the
fan. If it is still below 24 volts replace the boiler control
board.
Fault Code F20
CONDENSATE FULL F20
PUMP ON
The condensate trap is full. The red light will display
and the word LOCKOUT will flash. This code
indicates a serious safety issue. The boiler will not
restart until the cause is determined by a technician
and he pushes the RESET button on the display.
During this lockout fault, the pump will be off as
indicated on the second line of the display.
1. Check condensate lines for obstructions.
2. Check float switch in condensate reservoir.
3. Check wiring from condensate reservoir to 926
control and repair as necessary.
Fault Code F31
PROGRAM ERROR
F31
There was an error while programming the control
and the memory is corrupt. The boiler control will not
function in this state and the pump will be off as
indicated on the bottom line. This error only occurs if
a technician is programming the control and the
programming function fails. The only way to recover
from this error is to reprogram the control. If this
error occurs at any time other than when a
technician is servicing the boiler, the control has
failed and must be replaced by a qualified technician
The control must be re-programmed. If programming
does not solve problem, the control must be replaced.
Fault Code PP
CONTROL PROGRAMED
PP
The control has been programmed by a technician
or the factory. After programming, the control is left
in a locked out mode. Press the RESET key for at
least 1 second to begin use of the control.
The following blocking codes will block operation until the control determines the situation safe for boiler operation.
Blocking Code E07
FLUE TEMP HIGH E07
PUMP OFF TIME
This display indicates that the flue sensor tem-
perature is excessive and above 210
o
F. When this
code is displayed, the boiler will not respond to a
demand for heat. When the flue temperature
decreases below 194
o
F, the display will return to
normal and allow the boiler to respond to a heat
demand. The bottom line indicates the status of the
pump. The pump will remain off when this error is
displayed.
Check the flue for obstructions or any sign of damage,
especially signs of excessive heat. Repair as
necessary. Run the boiler and check the flue
temperature with an external thermometer. If the flue
temperature on the thermometer does not agree with
the flue temperature displayed in the status menu,
inspect the wiring to the flue temperature sensor in
the boiler and repair as necessary. If the wiring is
intact, replace the flue sensor. If the flue temperature
is excessive on the status menu and the test ther-
mometer reads the same, check and adjust
combustion controls on the boiler. If the problem
persists, inspect the target wall in the combustion
chamber and replace it if cracked or damaged.
Blocking Code E19
LINE VOLTAGE
PUMP OFF E19
This display indicates that the line voltage frequency
is out of range. This could happen if the boiler is
being powered from a small gasoline powered
generator that is not functioning correctly or
overloaded.
Inspect power wiring to boiler and repair as nec-
essary. If connected to line voltage, notify the power
company. If connected to an alternate power source
such as generator or inverter, make sure the line
voltage frequency supplied by the device is 60 Hz.
Table 26
– Fault and Blocking Code Screens
Summary of Contents for EL-110
Page 15: ...15 Figure 3 ...
Page 61: ...61 Figure 29 ...
Page 62: ...62 Figure 30 ...
Page 87: ...87 Figure 33 ...
Page 88: ...88 Figure 34 ...
Page 89: ...89 Figure 35 LP 293 A NOTE Parts listed on the following page ...
Page 94: ...94 ...
Page 95: ...95 ...
Page 96: ...96 MAINTENANCE NOTES ...