lp-666 Rev. 003 Rel. 001 Date 2.25.20
27
All vent pipes must be glued, properly supported, and the exhaust
pitched a minimum of 1/4” per foot back to the boiler to allow
drainage of condensate. When placing support brackets on vent
piping, the first bracket must be within 1 foot of the boiler and
the balance of 4 foot intervals on the vent pipe. Venting must be
readily accessible for visual inspection from the first three feet
from the boiler.
WARNING
!
Take extra precaution to adequately support the weight of vent
pipes terminating through the roof. Failure to properly support
roof terminated vent piping could result in property damage,
serious personal injury, or death due to flue gas leakage.
An unbalanced vent system can be installed ONLY when the
exhaust is in the vertical position. Failure to do so could result in
serious personal injury or death.
NOTE:
These drawings are meant to demonstrate system venting
only. The installer is responsible for all equipment and detailing
required by local codes.
Ensure the terminations are screened to prevent blockage caused
by debris or birds.
12" MIN.
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS
GREATER (TYP)
EXTERIOR WALL
EXHAUST
INTAKE
1" MIN.
06/23/15
LP-505-A
Insert Intake/Exhaust Screen
into Open End of Elbow
Insert Intake/Exhaust
Screen into Coupling
Two Pipe Sidewall Venting
with Intake (Elbow) and
Coupling (Exhaust)
400 - 1000 Models ONLY
Figure 17 - Sidewall Venting with Elbow and Coupling (400 - 1000
Models) and Couplings Only (1500 - 2000 Models ONLY)
12" MIN.
MAINTAIN 12" MINIMUM
CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL
OR GRADE, WHICHEVER IS
GREATER (TYP)
EXTERIOR WALL
EXHAUST
INTAKE
1" MIN.
10/30/18
LP-505-A
Two Pipe Sidewall Venting
with Couplings (Intake and Exhaust)
1500 - 2000 Models ONLY!
INSERT EXHAUST
SCREEN INTO
COUPLING
INSERT SCREEN INTO COUPLING
Figure 16 - Unbalanced Venting - Roof Exhaust and Sidewall Intake
MAINTAIN MIN 12" CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL OR GRADE
WHICHEVER IS HIGHER
24"
EXHAUST
AIR INTAKE
12" OVER MAXIMUM SNOW
LEVEL OR 24" WHICHEVER IS
GREATER
LP-666-G
10/18/18
Figure 15 - Roof Venting with Stainless Steel and Tee and Coupling