D. Boiler Gas Valve
Figure 40 - 400 and 500 Model Gas Valve
10/26/18
GAS OUTLET
LP-550-O
GAS INLET
OUTLET PRESSURE
THROTTLE ADJUSTMENT
INLET PRESSURE
TEST POINT
TEST POINT
OFFSET ADJUSTMENT
CAUTION: DO NOT REMOVE
THIS SCREW OR ATTEMPT TO
MAKE ANY ADJUSTMENT TO
THIS SCREW WITHOUT A
COMBUSTION ANALYZER.
B
SCALE 2 : 1
DETAIL B
THROTTLE ADJUSTMENT
NOTE: IF FOR ANY REASON THE
THROTTLE NEEDS TO BE ADJUSTED,
IT IS VERY IMPORTANT THAT A
COMBUSTION ANALYZER BE USED
TO ENSURE SAFE AND PROPER
OPERATION. TURN THE ADJUSTER
COUNTER CLOCKWISE TO INCREASE
THE GAS OR CLOCKWISE TO
DECREASE THE GAS SUPPLY. THIS
ADJUSTMENT COULD AFFECT
CO/CO% LEVELS. MAKE SURE THE
LEVELS CORRESPOND TO THE
CHART IN THIS MANUAL.
Figure 41 - 650 - 2000 Model Gas Valve - If Necessary, Use #40 Torx to Adjust Offset and Hex to Adjust the Throttle
DANGER
!
Do not do a gas conversion on this boiler without an officially
approved conversion kit and instructions supplied by HTP. Failure to
use a conversion kit when converting the boiler to fire on Natural
or Propane gas will result in extremely dangerous burner operation,
leading to fire, explosion, severe personal injury, or death.
Adjustments to the throttle screw or offset may only be made by
a qualified gas technician using a calibrated combustion analyzer
capable of measuring CO2 and CO. Failure to follow this instruction
will result in fire, explosion, property damage, severe personal
injury, or death.
DANGER
!