Error code
Meaning
Cause
Water Inlet Sensor error
(Automatic reset)
When DHW Inlet temperature
sensor wiring line located at DHW
inlet adapter is disconnected or
having issue.
Failure event
DHW inlet temperature sensor mulfunction or disconnected
Check point
① Check if DHW Inlet
temperature sensor’s
wiring connected at
DHW inlet adapter is
disconnected. And
check main control’s
socket.
DHW Inlet water (blue/blue)
② Connect multimeter leads
to the DHW Inlet temperature
sensor socket and measure the
resistance value (If value is 0Ω
it’s a sensor’s malfunction so
sensor needs to be replace)
Chapter 4 Troubleshootion
Error code
Meaning
Cause
Water Outlet Sensor error
(Automatic reset)
Error is displayed when DHW
outlet temperature sensor wiring
line is disconnected or faulty.
Failure event
Water outlet sensor faulty or disconnected.
Check point
① Check if Water Outlet Temperature Sensor wiring and main
controller connected at water outlet adapter is disconnected.
Also check main controller's socket.
② ▶ Connect multimeter leads
to the Water Outlet Sensor
socket and measure the
resistance value (If value is
0Ω it’s a sensor’s malfunction
so replace it)
③ If all things are normal, please replace main
controller.
Chapter 4 Troubleshootion
WARNING
Failure to turn the power off to the appliance before repair could result in serious injury or death.