3.1 Current setting value Ir and tolerance of the release
Table 4
Long time delay
Short time delay
Instantaneous
Grounding fault
Ir
Tolerance
Isd
Tolerance
Ii
Tolerance
Ig
Tolerance
(0.4
~
1)In+OFF
±10%
(1.5
~
15)Ir+OFF
±10%
(1.0
~
20)Ir+OFF
±15%
(0.2
~
1.0)In+OFF
±10%
Note: When three sections of protection are available at the same time, the setting values cannot cross, and Ir < Isd < Ii.