UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
151
Step 2
Close the input surge protection circuit breaker on the input PDC.
If no input surge protection circuit breaker is configured, go to the next step. If the input surge protection
circuit breaker is not closed, an alarm is generated and a message is displayed to prompt you to close it.
Step 3
After the LCD starts, perform the following steps:
If the UPS is starting for the first time, set the language, date and time, network
parameters, and system parameters on the
Settings Wizard
screen.
If this is not the first startup, retain the previous settings.
After you specify the settings, the
Bypass mode
and
No battery
alarms are displayed on the LCD.
The main buttons on the
Settings Wizard
screen are described as follows:
Tap
Previous
to return to the upper-level screen.
Tap
Next
to go to the next screen.
Tap
Cancel
to exit the
Settings Wizard
screen.
1.
Various languages are available, such as Chinese and English. Press
Down
and
Up
to
view the language types, as shown in
Figure 5-3
Language screen
2.
Tap
Next
on the
Time
screen, select a date format, as shown in
Set the date and time correctly. Incorrect time display in running and alarm information would
lead to analysis errors during maintenance or repair.