UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
159
Table 5-1
Battery parameter settings
Battery
Specifications
Number of
Batteries
Number of
Battery
Strings
Number of
Cells
Battery
Capacity
150 Ah/12 V
36 batteries in
series
Two battery
strings
connected in
parallel
36 x 6 = 216
150 Ah + 150
Ah = 300 Ah
300 Ah/2 V
192 batteries in
series
Two battery
strings
connected in
parallel
192 x 1 = 192
300 Ah + 300
Ah = 600 Ah
300 Ah/12 V
40 batteries in
series
Three battery
strings
connected in
parallel
40 x 6 = 240
300 Ah + 300
Ah + 300 Ah =
900 Ah
300 Ah/2 V
240 batteries in
series
Four battery
strings
connected in
parallel
240 x 1 = 240
300 Ah + 300
Ah + 300 Ah +
300 Ah = 1200
Ah
Step 9
After checking that the battery strings are properly connected, turn on the battery switch (if
there are multiple battery strings, turn on the switch for each battery string, and then turn on
the general switch between the battery strings and the UPS).
After you turn on the battery switch, the
No battery
alarm disappears on the MDU.
Step 10
Close the UPS output circuit breaker on the output PDC, or turn on the external output
distribution switch to supply power to loads.
If the UPS has powered on or is working in bypass mode and you need to transfer the UPS to normal
mode, check that no alarm has been generated and perform
If the UPS has powered off, perform all of the preceding steps.
----End