UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
178
Figure 5-38
EPO alarm on the WebUI
After you turn on the EPO switch, the
EPO
and
No power supplied
alarms are displayed on the LCD.
5.10 Clearing the EPO State
Procedure
Step 1
Turn off the EPO switch to clear the EPO state. Ensure that the EPO switch connected to the
dry contact card is not in the EPO state.
Step 2
Clear the EPO alarm.
LCD
On the main screen, tap
System Info.
and
. On the
Alarms
screen, tap
Clear Faults
.
If you have not logged in, enter a user name and password, and tap
on the
login screen displayed. In the displayed dialog box, tap
Yes
to clear the EPO alarm, as