UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
183
Figure 5-45
Confirmation message
Figure 5-46
Security warning on the LCD
Step 4
Check that the load power is stable (overload due to transient surge may cause the UPS to
transfer to bypass mode), and click
Yes
.
Step 5
Set the
Module cycle hiber. period (days)
parameter to an integer ranging from
0
to
100
.
The default value is
30
. If the value is
0
, the hibernation period is 2 minutes. That is, the
module starts automatically after 2-minute hibernation.
----End
5.11.2 WebUI
Procedure
Step 1
On the login page, enter a user name and password, and click
Login
.
Step 2
Choose
Monitoring
>
Param. Settings
>
Advanced Param.
, as shown in