UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
189
If the battery voltage is greater than
D.G. startup batt. volt.
, the UPS exits intelligent mode and
triggers D.G. shutdown signals. If the battery voltage is less than
D.G. startup batt. volt.
, a dialog
box is displayed, indicating potential risks. Tap
OK
to exit intelligent mode.
To disable the D.G. from the UPS system, set
Intelligent Power Supply
to
Disabled
. The system
changes
Working mode
to
Normal mode
,
Intra-rack power unit start delay (s)
to 5,
Output freq.
track rate (Hz/s)
to
0.6
,
Input adaptability
to
Non-strong input
,
D.G. mode
to
Disabled
, and
D.G.
connection [GEN]
to
Disabled
. You can change the values.
----End
5.12.2 WebUI
Procedure
Step 1
On the login page, enter a user name and password, and click
Login
.
Step 2
Choose
Monitoring
>
Param. Settings
. Under
Intelligent Power Settings
, set
Intelligent
Power Supply
to
Enabled
, as shown in
Figure 5-56
Intelligent power parameters on the WebUI
Intelligent Power Supply
parameter
The value can be
Enabled
or
Disabled
. The default value is
Disabled
.
ATS
parameter
The value can be
Connected
or
Not connected
. When the value is
Connected
, the UPS
works in the ATS scenario; when the value is
Not connected
, the UPS works in the reuse
scenario. The default value is
Connected
. This parameter is available only after you set
Intelligent Power Supply
to
Enabled
.
D.G. startup batt. volt. (V/cell)
parameter
The value ranges from
1.80
to
2.00
. The default value is
1.80
. This parameter is available
only after you set
Intelligent Power Supply
to
Enabled
.
Set the preceding three parameters when you connect the D.G. to the UPS.