UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40
Connector
Connection
Mode
Bolt Type
Bolt Hole
Diameter
Torque
connector
terminals
Bypass input
connector
Crimped OT
terminals
M12
13.5 mm
46 N•m
Battery input
connector
Crimped OT
terminals
M12
13.5 mm
46 N•m
Output
connector
Crimped OT
terminals
M12
13.5 mm
46 N•m
Grounding
connector
Crimped OT
terminals
M12
13.5 mm
46 N•m
lists the recommended upstream input circuit breaker configurations for the
UPS5000-E.
Table 3-6
Upstream input circuit breaker configurations
Upstream
Input
Circuit
Breaker
UPS5000-E-120K-F120
UPS5000-E-200
K-F200
UPS5000-E-320K-F320/
UPS5000-E-320K-F320T
40
kVA
80
kVA
120
kVA
160
kVA
200
kVA
240
kVA
280
kVA
320
kVA
Upstream
mains input
switch
Three-
pole,
100 A
Three-
pole,
160 A
Three-
pole,
250 A
Three-
pole,
400 A
Three-
pole,
400 A
Three-
pole,
500 A
Three-
pole,
500 A
Three-
pole,
630 A
Upstream
bypass
input
switch
Three-
pole,
100 A
Three-
pole,
160 A
Three-
pole,
250 A
Three-
pole,
400 A
Three-
pole,
400 A
Three-
pole,
500 A
Three-
pole,
500 A
Three-
pole,
630 A
Table 3-7
Upstream input circuit breakers
Model
UPS
Capacity
Component
Specification
s
Manufactur
er
UPS5000-E-1
20K-F120
40 kVA
Mains input circuit
breaker
T1N160 TMD
R100 FFC 3P
ABB
(recommende
d when the
short-circuit
current where
the switch is
located is
less than 36
kVA.)
Bypass input circuit
breaker
T1N160 TMD
R100 FFC 3P
80 kVA
Mains input circuit
breaker
T1N160 TMD
R160 FFC 3P
Bypass input circuit
breaker
T1N160 TMD
R160 FFC 3P