UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
53
----End
3.2.3 (Optional) Installing an IP21 Component
Context
If an IP21 component is installed for the UPS5000-E-120K-F120 and UPS5000-E-200K-F200,
top cable routing is not supported.
Procedure
Step 1
Install leveling feet at the bottom of the IP21 component, with two long feet on the front and
two short feet at the rear, as shown in
Figure 3-17
Installing leveling feet
Refer to the "front" and "back" silk screens on the surface of the IP21 component.
Step 2
Install the IP21 component at the top of the UPS cabinet using four M12 screws, as shown in