UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
68
Figure 3-34
Routing signal cables from the top of the cabinet
----End
3.2.8.2 Bottom Cable Routing
Context
If you route cables through the bottom of the cabinet, ensure sufficient space.
After routing cables, use fireproof mud to fill in the gap between the cables and the
cabinet.
The UPS5000-E-320K-F320T does not support cable routing from the bottom.
The UPS5000-E-120K-F120, UPS5000-E-200K-F200, and UPS5000-E-320K-F320 use the
same bottom cable routing mode. Bottom cable routing for the UPS5000-E-200K-F200 is
used as an example. To route cables from the bottom of the UPS5000-E-200K-F200, perform
the following steps:
Procedure
Step 1
Open the front door, and remove the cover from the power distribution subrack, as shown in