UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
94
Figure 3-67
Connecting signal cables in a dual-bus system
Step 2
Connecting the signal cables to each single UPS in a parallel system. For details, see section
3.2.13 Connecting Signal Cables
----End
3.4 Verifying the Installation
Check items 09 and 10 carefully. Otherwise, the UPS may fail.
No.
Item
Expected Result
01
Consistency between system
configurations and delivery
configurations
System configurations, including models and
number of modules, comply with the contract.
02
Cable layout
Cables are routed properly and meet
engineering requirements.
03
Cable connections
Input and output power cables and battery
cables are securely connected and spring