After you shut down the inverter, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power.
Before you shut down the UPS, ensure that all loads have shut down.
Procedure
Step 1
Shut down the inverter.
Method for shutting down the inverter on the LCD
a.
On the main screen, tap
Common Functions
. Tap
Inv. Off
.
b.
If you have not logged in, enter a user name and password, and tap
on the
login screen displayed.
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
c.
In the displayed dialog box, tap
Yes
to shut down the inverter, as shown in
Figure 5-15
Inverter Off screen
You can also tap
System Info.
>
Maintenance
and shut down the inverter on the
Maintenance
screen.
Method for shutting down the inverter on the WebUI
a.
In a web browser, enter the UPS IP address.
b.
On the login page, select a display language, enter a
user name
and
password
, and
click
Login
.
lists the default user names and preset passwords and describes the permission of the
default users.
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.