UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
161
c.
On the homepage, choose
Monitoring
>
Control
, and click
Inverter Off
. In the
displayed dialog box, click
OK
to shut down the inverter, as shown in
Figure 5-16
Shutting down the inverter
Step 2
After the inverter shuts down, if the bypass is normal, the UPS transfers to bypass mode; if
the bypass is abnormal, the UPS supplies no power, and the loads shut down, as shown in
Figure 5-17
Bypass mode
After you shut down the inverter, the
Bypass mode
alarm is displayed on the LCD.
Step 3
After the inverter shuts down, open the UPS output switch on the output PDC, or turn off the
external output distribution switch.