UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
180
Figure 5-41
Clearing the alarm
Step 3
View active alarms and ensure that the EPO alarm is cleared. If the input of the system bypass
is normal, the UPS transfers to the bypass mode.
LCD
On the main screen, tap
System Info.
and
. On the
Alarms
screen, tap
Active Alarms
to check that the EPO alarm disappears from the alarm list, as shown in
Figure 5-42
Active Alarms screen
WebUI
In a web browser, enter the UPS IP address. On the login page, select a display language,
enter a user name and password, and click
Login
. On the homepage, choose
Monitoring
>
Active Alarms
to check that the EPO alarm disappears from the alarm
list.
If the bypass is normal, the UPS transfers to bypass mode, as shown in