UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
184
Figure 5-47
Hibernation parameters on the WebUI
Step 3
On the WebUI, set
Para. sys. hibernate
to
Enable
, and click
Submit
. A security waning is
displayed, and click
OK
.
Step 4
Set the
Module cycle hiber. period (days)
parameter to an integer ranging from
0
to
100
.
The default value is
30
. If the value is
0
, the hibernation period is 2 minutes. That is, the
module starts automatically after 2-minute hibernation.
Click
Submit
after you set the parameter on the WebUI.
----End
5.12 Setting Intelligent Mode
Context
Before you connect the D.G. to a UPS system, check that the system is a single UPS system
and that the system is working in non-inverter mode and has connected to batteries.
When the UPS is working, the D.G. starts if a main outage occurs and the battery voltage
reaches the specified threshold. To set intelligent mode on the LCD or WebUI, perform the
following steps:
5.12.1 LCD
Procedure
Step 1
On the main screen, tap
System Info.
and
. The
Settings
screen is displayed.
If you have not logged in, enter a user name and password, and tap
on the login screen
displayed