UPS5000-E-(40 kVA-320 kVA)
User Manual
5 Operations
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
192
Table 5-3
Associated intelligent power supply parameters
Parameter
Value
Remarks
Working mode
ECO
N/A
D.G. mode
Enabled
You cannot change the value.
Intra-rack power unit
start delay (s)
5
N/A
Input adaptability
Strong
N/A
Output freq. track rate
(Hz/s)
0.6
N/A
D.G. connection [GEN]
Enabled
N/A
MUS05A DO_4
D.G. control
N/A
ATS
Connected
N/A
D.G. startup batt. volt.
(V/cell)
1.80
N/A
D.G. power limiting
(kVA)
N/A
Indicates the actual D.G.
power. Set it as required.
D.G. charger power ratio
N/A
Indicates the percentage of the
battery power provided by the
charger. Set it as required.
In battery mode (not battery test state), when the battery voltage reaches
D.G. startup batt. volt.
or
Low battery voltage
, the UPS triggers D.G. startup signals.
In normal mode or bypass mode, if the mains is normal (the mains supplies power for 1 minute and
the D.G. runs for 15 minutes), the UPS triggers D.G. shutdown signals.
If the battery voltage is greater than
D.G. startup batt. volt.
, the UPS exits intelligent mode and
triggers D.G. shutdown signals. If the battery voltage is less than
D.G. startup batt. volt.
, a dialog
box is displayed, indicating potential risks. Tap
OK
to exit intelligent mode.
To disable the D.G. from the UPS system, set
Intelligent Power Supply
to
Disabled
. The system
changes
Working mode
to
Normal mode
,
Intra-rack power unit start delay (s)
to 5,
Output freq.
track rate (Hz/s)
to
0.6
,
Input adaptability
to
Non-strong input
,
D.G. mode
to
Disabled
, and
D.G.
connection [GEN]
to
Disabled
. You can change the values.
----End
5.12.3 Reuse Scenario
In reuse scenarios, the D.G. connects to the UPS over the bypass module. Dry contacts control
D.G. startup and shutdown.