UPS5000-E-(40 kVA-320 kVA)
User Manual
8 Technical Specifications
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
206
8.2 Environmental Specifications
Item
UPS5000-E-120K-
F120
UPS5000-E-20
0K-F200
UPS5000-E-32
0K-F320
UPS5000-E-320
K-F320T
Operating
temperature
0–40°C
Storage
temperature
–40°C to +70°C
Humidity
0%–95% RH (non-condensing)
Altitude
1000–4000 m
When the altitude is above 1000 m, the load that the UPS can support
decreases by 1% for each additional 100 m.
Noise
< 65 dB
< 68 dB
8.3 Safety Regulations and EMC
Item
UPS5000-E-120K-
F120
UPS5000-E-20
0K-F200
UPS5000-E-3
20K-F320
UPS5000-E-3
20K-F320T
Safety
regulations
EN62040-1: 2008
IEC62040-1: 2008
YD/T2165-2010
GB/T14715-93
EN62040-1:
2013
IEC62040-1:
2013
YD/T1095-200
0
EMC
EN62040-2
IEC62040-2
IEC61000-3-11
IEC61000-3-12
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
EN61000-4-6
IEC61000-4-8
IEC61000-4-11