UPS5000-E-(40 kVA-320 kVA)
User Manual
8 Technical Specifications
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
207
8.4 Mains Input Electrical Specifications
Item
UPS5000-E-120K-F12
0
UPS5000-E-2
00K-F200
UPS5000-E-3
20K-F320
UPS5000-E-3
20K-F320T
Input
system
Three-phase, five-wire
Rated input
voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input
voltage
138–485 V AC (line voltage)
The UPS power is not derated at 305–485 V AC and is linearly derated at
305–138 V AC.
Input
frequency
40–70 Hz
Input PF
0.99
THDi
< 3% (full linear load); < 5% (full non-linear load)
8.5 Bypass Input Electrical Specifications
Item
UPS5000-E-120K-F12
0
UPS5000-E-20
0K-F200
UPS5000-E-32
0K-F320
UPS5000-E-32
0K-F320T
Input
system
Three-phase, five-wire
Rated
input
voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input
frequen
cy
50 Hz or 60 Hz (tolerance ± 6 Hz)
Bypass
synchro
nization
tracking
frequen
cy
50 Hz or 60 Hz (tolerance ± 6 Hz)