UPS5000-E-(40 kVA-320 kVA)
User Manual
8 Technical Specifications
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
208
8.6 Battery Specifications
Item
UPS5000-E-120K-F
120
UPS5000-E-2
00K-F200
UPS5000-E-3
20K-F320
UPS5000-E-3
20K-F320T
Battery
voltage
360–552 V DC (30–46 batteries, 32 by default); 6% derated when 30
batteries are configured.
Battery
monitoring
The BMU (optional) monitors batteries.
Battery
management
Intelligent battery management
One-button
cold start
In the case of a mains failure, batteries can start the UPS to power loads.
Battery string
sharing
The UPSs connected in parallel can share battery strings. By default,
battery strings are not shared.
Charge
voltage
Equalized voltage: 2.35 V/cell
Float voltage: 2.25 V/cell
In monitoring and power versions earlier than V100R001C10SPC008 (software package version:
V100R001C10SPC700), the battery voltage is 360–480 V DC (30 to 40 batteries, 32 by default).
8.7 Output Electrical Specifications
Item
UPS5000-E-120K-F
120
UPS5000-E-20
0K-F200
UPS5000-E-32
0K-F320
UPS5000-E-32
0K-F320T
Output
system
Three-phase, five-wire
Voltage
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%) (line voltage)
Frequency
In normal mode, the mains frequency is synchronized with the bypass input
frequency.
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance ± 0.25%).
Total
harmonic
distortion
of output
voltage
(THDv)
< 1% (full linear load); < 3% (full non-linear load)
Output PF
1
Transfer
time
0 ms