UPS5000-E-(40 kVA-320 kVA)
User Manual
B Alarm List
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
232
Alarm
ID
(Alarm
ID-Caus
e ID)
Alarm
Name
Severit
y
Cause
Solution
threshold.
The
configure
d number
of
batteries
is less
than the
actual
number.
The actual
number of
batteries
does not
meet
requireme
nts.
0036-2
Battery
maintenanc
e reminder
Warning
The time for
maintenance
arrives.
Maintain the batteries.
0037-1
Battery
undervoltag
e
Critical
The UPS
works
long in
battery
mode.
The
charger is
faulty.
1.
Check whether the battery
voltage is normal.
2.
Check whether the output is
overloaded.
3.
Check whether any battery is
damaged. If yes, replace the
battery.
4.
Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
0040-7
Rectifier
abnormal
Critical
The fan
for the
power
module is
abnormal.
The air
channel of
the power
module is
obstructed
.
1.
Check that the air channel for
the module is free from
blockage.
2.
Check whether the fan is
abnormal. Replace the power
module if the fan is faulty.
0043-1
Fan
abnormal
Critical
The fan
for the
power
module is
Replace the faulty power module.