UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
41
Model
UPS
Capacity
Component
Specification
s
Manufactur
er
120 kVA
Mains input circuit
breaker
T3N250 TMD
R250 FF 3P
Bypass input circuit
breaker
T3N250 TMD
R250 FF 3P
UPS5000-E-2
00K-F200
160 kVA
Mains input circuit
breaker
T5N400 TMA
R320 FF 3P
Bypass input circuit
breaker
T5N400 TMA
R320 FF 3P
200 kVA
Mains input circuit
breaker
T5N400 TMA
R400 FF 3P
Bypass input circuit
breaker
T5N400 TMA
R400 FF 3P
UPS5000-E-3
20K-F320/U
PS5000-E-32
0K-F320T
240 kVA
Mains input circuit
breaker
T5N630 TMA
R500 FF 3P
Bypass input circuit
breaker
T5N630 TMA
R500 FF 3P
280 kVA
Mains input circuit
breaker
T5N630 TMA
R500 FF 3P
Bypass input circuit
breaker
T5N630 TMA
R500 FF 3P
320 kVA
Mains input circuit
breaker
T6N630
PR221DS-LS/
I R630 FF 3P
Bypass input circuit
breaker
T6N630
PR221DS-LS/
I R630 FF 3P
The input upstream circuit breakers recommended in
If multiple loads are connected, specifications for branch circuit breakers must not exceed the
recommended specifications.
The circuit breaker selection principle is to protect loads and cables, and the cascading principle is to
realize specific protection.