UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Figure 3-30
Routing signal cables from the top of the cabinet
Install a cable trough near the front of the UPS5000-E cabinet. If the cable trough is near the rear of the
UPS5000-E cabinet, move it to a place near the front of the cabinet.
Step 9
Install the side panel removed from the right of the UPS5000-E cabinet on the outer side of
the top entry cabinet.
----End
UPS5000-E-320K-F320T
To route cables from the top of the UPS5000-E-320K-F320T, perform the following steps:
Step 1
Open the front door, and remove the cover from the power distribution subrack, as shown in