UPS5000-E-(40 kVA-320 kVA)
User Manual
3 Installation
Issue 10 (2015-09-15)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Figure 3-37
Routing power cables from the bottom of the cabinet
(1) Mains input
PE
(2) Mains input L1
(3) Mains input
L2
(4) Mains input L3
(5) Mains input
N
(6) Bypass input PE
(7) Bypass
input L1
(8) Bypass input L2
(9) Bypass
input L3
(10) Bypass input N
(11) Output PE
(12) Output W
(13) Output V
(14) Output U
(15) Output N
(16) Battery input
positive terminal
(17) Battery
input N
(18) Battery input
negative terminal
When you choose to route cables by drilling holes, drill holes on the bottom plate, and paste grommet
strip to the hole edge to protect cables. Then route cables through the holes, use fireproof putty to fill in
the gap between cables and the cabinet.
Step 4
Route the cables on the left of subracks along the left side of the cabinet and the cables on the
right side of subracks along the right side of the cabinet, and then bind the cables to the
cabinet, as shown in