No
.
Port
Silkscreen
Matched
Terminal and
Cable
Description
2
AC input
terminals
L, N, PE
One-hole OT
terminal (M4). The
maximum cross-
sectional area of the
cable supported is 4
mm
2
(0.0062
2
).
The maximum input current
for a single input is 30 A.
3
DC output
terminals
LOAD0 to
LOAD5
shows
the EPC5
connectors for ports
LOAD0 to LOAD5.
The maximum
cross-sectional area
of the cable is 10
mm
2
(0.016 in.
2
).
The output current is 30 A.
4
DC output
terminals
LOAD6 to
LOAD9
shows
an EPC4/EPC6
connector, which
applies to any one
among ports
LOAD6 to LOAD9.
The maximum
cross-sectional area
of the cable is 4
mm
2
(0.006 in.
2
).
NOTE
an EPC4 or EPC6
connector. An EPC4
connector must be
connected to a cable
onsite, whereas an
EPC6 connector has
been connected to a
cable before
delivery. The EPC5
connector must be
connected to the
cable onsite.
The output current is 30 A.
5
Spare fuse
box
-
-
There are three fuses in the
spare fuse box:
l
Two 5 A spare fuses, each
used for transferring
power less than 150 W.
l
One 30 A spare fuse, used
for the 30 A output power
ports on the PDU10D-01.
BTS3900C (Ver.C)
Hardware Description
4 BTS3900C Power System
Issue 03 (2013-05-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
105