DPU40D-N06A3, DBU20B-N12A3, and
DBU50B-N12A1 Distributed Power System
User Manual
5 Maintenance
Issue 04 (2020-02-29)
Copyright © Huawei Technologies Co., Ltd.
31
5.1.2 Distributed Power Unit
Table 5-2
Distributed Power Unit maintenance
No.
Item
Possible Fault Cause
Suggestion
1
Check the green
indicator status
(normal: steady
on).
Off: The PSU has no
power input (no AC
input and no battery
input).
Steady on: Start /
Self-check / Load
(instantaneous status
during startup or
upgrade).
Blinking fast (4 Hz):
The PSU is not
communicating with the
host properly.
1.
Check the AC input of the
PSU.
2.
Check that the PSU
communications cable is
correctly connected and the
upstream monitoring
equipment works properly.
3.
Replace the PSU.
2
Check the red
indicator status
(normal: off).
Steady on: Rectifier
Fault/Monitoring
Address
Conflict/Monitoring
Unit Fault.
Blinking at short
intervals (0.5 Hz):
Rectifier
Protection/Power
off/Communication
Failure/Rectifier Power
Failure/Parallel Fail/AC
Overvoltage or
Undervoltage
1.
If multiple PSUs are
connected in parallel, check
that the communications
and power cables are
properly connected between
them.
2.
Replace the PSU.
5.1.3 Lithium Battery
Table 5-3
Lithium battery maintenance
No.
Item
Possible Fault Cause
Suggestion
1
Check the green
indicator status
(normal: blinks
slowly at 0.5
Hz).
Off: The lithium battery
has no DC input or is
faulty.
Steady on: Board startup /
self-check / loading /
activation / board
power-on when no
software is loaded.
1.
Check the AC input of the
lithium battery.
2.
Check the power cable
connection.
3.
Check the fuses for the ports
on the PSU and lithium
battery.
4.
Check the PSU output.
5.
Replace the lithium battery.
6.
Check the communications