![background image](http://html.mh-extra.com/html/huawei/ecc800-pro/ecc800-pro_user-manual_167982223.webp)
Table 6-43 Setting iBOX parameters
Parameter
Description
Remarks
iBOX single
battery qty.
Total number of batteries
monitored by the iBOX
Set this parameter
based on the battery
parameter planned by
the customer.
Batt installation
time
Actual time at which batteries are
installed
-
Single battery
capacity
Single battery capacity refers to the
capacity of a single battery in a
battery string managed by the
iBOX.
Obtain the battery
capacity from the
battery label or
document.
Current source
0–xxxA Hall
The actual specifications of the Hall
effect sensor prevail.
-
Battery string
No.
Set this parameter based on the
planned codes for iBOXs and
battery strings.
Set this parameter
based on the
customer's plan.
----End
6.9.2 Networking iBOXs and iBATs in Wireless Mode
Prerequisites
Before networking, ensure that all the iBOXs and iBATs have no network
parameters, that is, the RF_Z indicator on the iBOX is steady green and the
RUN/ALM indicator on the iBAT is steady red.
NO TE
● The iBAT is connected to the iBOX in RF_Z networking mode.
● If the RF_Z indicator on the iBOX is not steady on (green), press and hold down the
networking switch on the iBOX for 10–20 seconds to clear the original network.
● If the RUN/ALM indicator on the iBAT is not steady red, hold down the iBAT networking
switch for at least 5 seconds to clear the original network.
Context
●
If multiple iBOXs are connected, commission the iBOX one by one in the same
way. Otherwise, networking may be in disorder.
●
Indicator status:
–
Blinking at long intervals: The indicator is on for 1 second and then off
for 1 second alternately.
–
Blinking at super short intervals: The indicator is on for 0.05 seconds and
then off for 0.05 seconds alternately.
ECC800 Data Center Controller
User Manual (for ECC800-Pro)
6 Feature Description
Issue 02 (2020-09-07)
Copyright © Huawei Technologies Co., Ltd.
212