![background image](http://html.mh-extra.com/html/huawei/ecc800-pro/ecc800-pro_user-manual_167982294.webp)
1. After the PMAC615 is started, press
on the displayed screen and the
configuration screen is displayed. Press
until the ID prompt is displayed,
indicating the communications address setting screen.
2. Press
and a blinking cursor is displayed. Press
to modify the
communications address based on site requirements. Then press
to
confirm the address setting.
Figure 8-16 PMAC615 communications address
Step 2 Add a PMAC615.
1. Log in to the ECC800-Pro WebUI as an administrator.
2. Add a PMAC615.
Table 8-17 Adding a PMAC615
Path
Parameter
Setting
Choose
System
Settings >
Device
Management
and click Add
Device. The
parameters
for adding
devices are
displayed.
Device
attribute
Select Electricity Meter from the drop-
down list box.
Device Type
Select PMAC615 from the drop-down list
box.
Connect To
Select ECC800 from the drop-down list
box.
Communicati
ons Port
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the
PMAC615 is connected to the COM3 port on
the ECC800-Pro. If the PMAC615 is connected to
another port, enter the number of the
connected port.
Device
Address
In this example, Device Address is set to 8.
During actual configuration, set the device
address for the PMAC615 based on the
actual situation.
3. Click Test Connect to check whether the PMAC615 connects to the ECC800-
Pro properly.
–
If the PMAC615 connects to the ECC800-Pro successfully, click Confirm.
The connected devices are displayed in the Number of connected
devices list.