ETP48400-C9A2 Embedded Power
User Manual
3 Components
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
19
Item
Specifications
32 A circuit breakers
Battery route
Four 1-pole 125 A circuit breakers
3.2 Rectifier
Rectifiers convert AC input into stable DC output.
Figure 3-4
Rectifier
(1) Run indicator
(2) Alarm indicator
(3) Fault indicator
(4) Locking latch
(5) Handle
Table 3-2
Rectifier indicator description
Indicator Color
Status
Description
Run
indicator
Green
Steady on
The rectifier has an AC power input.
Off
The rectifier has no AC power input.
The rectifier is faulty.
Blinking at 0.5
Hz
The rectifier is being queried.
Blinking at 4
Hz
The rectifier is loading an application program.
Alarm
indicator
Yellow
Off
No alarm has been generated.
Steady on
The rectifier has generated an alarm due to
ambient overtemperature.
The rectifier has generated an alarm for