Pin
Signal
Description
2
TX-
3
RX+
Receives data over FE.
6
RX-
4, 5, 7, 8
NA
-
Table 3-7
Pin definitions for the RS485/RS232 port
Pin
Signal
Description
1
TX+
Transmits data over RS485.
2
TX-
4
RX+
Receives data over RS485.
5
RX-
3
RX232
Receives data over RS232.
7
TX232
Transmits data over RS232.
6
PGND
Connects to the ground.
8
NA
–
3.4 UIM02C
Panel
The user interface module (UIM02C) supports eight dry contact outputs, six dry contact
inputs, and seven sensor ports (including one ambient temperature and humidity input, one
water sensor input, two ambient temperature inputs, one door status sensor input, one smoke
sensor input, and one battery temperature input).
Figure 3-7
UIM02C panel